﻿GET_GEVOMechL2_09_01_01_48 - ANIMATION Screen
1
00:00:00,000 --> 00:00:04,417
Describe how to perform running maintenance related to the alternator.

2
00:00:04,417 --> 00:00:15,375
Every 92 days, the 5GMG203, 5GMG205, and 5GMG206 alternators should be inspected.

3
00:00:15,375 --> 00:00:20,958
Brushes, brush length, and the surface condition of the collector rings should be checked.

4
00:00:20,958 --> 00:00:22,625
Brush Inspection

5
00:00:22,625 --> 00:00:25,917
Ensure that the pigtails are positioned correctly.

6
00:00:25,917 --> 00:00:30,667
They must be parallel with, but not rubbing against, the pressure arm.

7
00:00:30,667 --> 00:00:34,458
Ensure that the pigtail terminal bolts are tight.

8
00:00:34,458 --> 00:00:44,750
Move the brushes up and down several times in the brush holders to release any carbon dust or foreign matter in the carbon ways that could prevent free movement of the brushes.

9
00:00:44,750 --> 00:00:46,292
Brush Removal

10
00:00:46,292 --> 00:00:49,208
1. Unlatch the brush pressure spring thumb loop.

11
00:00:49,208 --> 00:00:52,500
2. Loosen the terminal bolt on the brush holder.

12
00:00:52,500 --> 00:00:55,125
3. Slide the brush out of the brush holder.

13
00:00:55,125 --> 00:00:56,958
Brush Installation

14
00:00:56,958 --> 00:01:04,458
1. Insert each brush into a brush holder so that the contour of the brush or its riding surface matches that of the collector ring.

15
00:01:04,458 --> 00:01:10,292
2. Position the pigtail terminal under the terminal screw and parallel to the brush pressure arm.

16
00:01:10,292 --> 00:01:19,125
3. Tighten the terminal screw, and torque it to 6-8 lb.-ft. (8.13-10.85 Nm).

17
00:01:19,125 --> 00:01:24,042
4. Latch the brush pressure spring thumb loop over the detent in the brush holder body.

18
00:01:24,042 --> 00:01:34,792
5. Dress the pigtail leads such that the pigtail wires do not interfere with the action of the pressure arm, rub against each other, or rub against adjacent brush holders.

19
00:01:34,792 --> 00:01:37,167
Brush Holder Inspection

20
00:01:37,167 --> 00:01:41,792
Check for loose, broken, bent, or overheated pressure arms.

21
00:01:41,792 --> 00:01:47,000
Overheating will cause the arms to discolor and result in improper brush arm pressure.

22
00:01:47,000 --> 00:01:50,000
Annually verify brush arm force.

23
00:01:50,000 --> 00:02:01,000
If it is below 4.25-4.75 lbs. (1.93-2.15 kg), replace the brush holder.

24
00:02:01,000 --> 00:02:07,917
Ensure that the thumb loop on the coiled brush pressure spring is in position with the spring end placed into the detent.

25
00:02:07,917 --> 00:02:15,625
Inspect the brush holder mounting arrangement, and ensure the clamp pads are in place and tight against the brush holder stud.

26
00:02:15,625 --> 00:02:21,042
If they are not in place, locate the clamp pads and torque the clamp bolts.

27
00:02:21,042 --> 00:02:24,333
Check the brush holder-to-collector ring clearance.

28
00:02:24,333 --> 00:02:39,083
If the clearance is not between 0.089 and 0.091 inches (2.2-2.3 mm), adjust the clearance as discussed in the Brush Holder and Stud Assembly Alignment section of this module.

29
00:02:39,083 --> 00:02:44,250
Inspect the brush holder assembly for broken connection straps or bus rings.

30
00:02:44,250 --> 00:02:53,792
Replace, if necessary, as discussed in the Brush Holder and Stud Assembly Removal and the Brush Holder and Stud Assembly Installation sections of this module.

31
00:02:53,792 --> 00:02:58,250
Check by hand the tightness of the bus ring to the brush holder bolts.

32
00:02:58,250 --> 00:03:00,750
If loose, torque the bolts.

33
00:03:00,750 --> 00:03:03,333
Brush Holder Stud Inspection

34
00:03:03,333 --> 00:03:06,042
Wipe the brush holder studs clean.

35
00:03:06,042 --> 00:03:11,417
Inspect the brush holder stud for cracked, discolored, or worn insulation.

36
00:03:11,417 --> 00:03:15,625
Replace the complete stud if insulation is found to be faulty.

37
00:03:15,625 --> 00:03:22,958
If brush holders are found to be loose or are moveable by hand, inspect the stud for discoloration and wear.

38
00:03:22,958 --> 00:03:25,750
Replace the stud, if damaged.

39
00:03:25,750 --> 00:03:33,500
If there is no damage, reinstall the stud as discussed in the Brush Holder and Stud Assembly Installation section of this module.

40
00:03:33,500 --> 00:03:36,625
Brush Holder and Stud Assembly Maintenance

41
00:03:36,625 --> 00:03:49,583
If a single brush holder or a brush holder stud needs to be replaced, remove the entire brush holder and stud assembly from the alternator, replace the faulty component, and return the whole assembly to the alternator.

42
00:03:49,583 --> 00:03:56,583
1. With the brush holder/collector ring cover removed, blow out the compartment with clean, dry and compressed air.

43
00:03:56,583 --> 00:04:03,000
2. Wipe off the insulation between the collector rings and the collector ring studs with a clean, dry rag.

44
00:04:03,000 --> 00:04:10,625
3. Using an appropriate solvent, wipe away any residue from the brush holders with a clean, dry and lint-free cloth.