﻿GET_GEVOMechL2_03_01_01_42 - ANIMATION Screen
1
00:00:00,000 --> 00:00:07,250
Self-Test 309, initiated by means of a Smart Display, can be used to test the green LED.

2
00:00:07,250 --> 00:00:14,833
When illuminated, the green LED normally indicates that the water is out of the radiators and is in the water storage tank.

3
00:00:14,833 --> 00:00:22,292
Self-Test 309 is used to test that the computer system can turn on and off the green LED only.

4
00:00:22,292 --> 00:00:27,792
This self-test does not test the operation of the water flow control magnet valves.

5
00:00:27,792 --> 00:00:41,500
Self-Test 320, initiated by means of a Smart Display, can be used to test the univalve and water flow control magnet valves (WFV1, WFV2, and WFV3).

6
00:00:41,500 --> 00:00:52,792
This self-test is used to place the split cooling water system in a Mode of operation (Mode 1, 2, or 3) and then verify that the proper switching has occurred.

7
00:00:52,792 --> 00:01:04,458
In Mode 1, the univalve mode indicator should be in the 12 o'clock position, and WFV1, WFV2, and WFV3 should be energized.

8
00:01:04,458 --> 00:01:12,458
In Mode 2, the univalve mode indicator should be in the 2 o'clock position, and WFV2 should be energized.

9
00:01:12,458 --> 00:01:20,625
In Mode 3, the univalve mode indicator should be in the 4 o'clock position, and all WFV's should be de-energized.

10
00:01:20,625 --> 00:01:28,292
Self-Test 404, initiated by means of a Smart Display, can be used to test the radiator fan operation.