When the radiator is not flooded and water is not flowing through it for an extended period of time (i.e., ambient temperature dependent), the radiator metal temperature approaches the ambient temperature.

2
00:00:11,750 --> 00:00:22,292
When water is again diverted to the radiator, especially during low ambient operation, the temperature difference induces significant heat transfer from the water to the radiator.

3
00:00:22,292 --> 00:00:33,792
The temperature of the water at the exit of the radiator is low enough that, even after mixing with the water in the tank, it is still below the Mode 2 to Mode 3 transition temperature set point.

4
00:00:33,792 --> 00:00:38,167
An immediate transition would stop the flow of water to the radiator.